EX-6100
ENMET Corporation
15
9 Certification
The EX-6100/FGD10 Series of Gas Detectors are ATEX and IECEx certified for use in potentially explosive atmospheres and
is marked as follows:-
** Denotes additional characters that define the gas detector configuration e.g. Enclosure type and sensor arrangement.
YYYY – Denotes year of manufacture.
Special Conditions of Safe Use
Only Loctite 243 or a compound of equal strength shall be reapplied to the threads of the sensor after replacing the sensing
element
Electrical data
Power supply - 8Vdc to 24Vdc, 5W
Relay contact rating – 300Vac, 3 Amps
Installation instructions
The cable entry devices and blanking elements of unused apertures shall be of a certified flameproof type, suitable for the
conditions of use and correctly installed.
With the use of conduit, a suitable certified sealing device such as a sealing fitting with compound shall be provided
immediately at the entrance to the flameproof enclosure.
10 EX-6100 Accessories and Calibration Gas
EX-6100 accessories and calibration gas ENMET part number
Sensor 03070-007
Calibration Adaptor 03700-057
Regulator Assembly 02506-004
Calibration Gas, 50%LEL Methane 03220-050
Calibration Gas, 50%LEL Propane 03221-050
Calibration Gas, 50%LEL Hydrogen 03227-050
Calibration Gas, 50%LEL Butane 03282-050
Weather Guard 04546-012
Maintenance Tool, Sensor 73413-210
WARNING – DO NOT OPEN WHEN AN EXPLOSIVE GAS
ATMOSPHERE IS PRESENT
GAS DETECTOR TYPE FGD10 **
STATUS SCIENTIFIC
IECEx SIR 08.0009X
CONTROLS LTD.
T4 (Ta -20
O
C to +60
O
C)
MANSFIELD
T5 (Ta -20
O
C to +50
O
C)
NG18 5ER.UK.
T6 (Ta -20
O
C to +35
O
C)
II 2 G Ex d IIC 1180
SIRA 08ATEX1031X
SERIAL No. XXXXXX CIRCUIT RATING: 24VDC, 5W
YYYY RELAY CONTACT RATING:
300VAC. 3A MAX.